A tognum Group Brand
Diesel Engine-Generator Set
40-JS6DT3
40 ekW / 60 Hz / Standby
208 - 600V
System Ratings
Standby
Voltage (L-L)
Phase
PF
Hz
kW
kVA
AMPS
skVA@30%
Voltage Dip
Generator Model
Temp Rise
Connection
** UL2200 Offered
Facts
240V**
1
1.0
60
40
40
167
63
361CSL1601
130°C/27°C
12 LEAD ZIG-ZAG
208V**
3
0.8
60
40
50
139
105
361CSL1601
130°C/27°C
12 LEAD LOW WYE
240V**
3
0.8
60
40
50
120
105
361CSL1601
130°C/27°C
12 LEAD HI DELTA
480V**
3
0.8
60
40
50
60
140
361CSL1601
130°C/27°C
12 LEAD HI WYE
600V**
3
0.8
60
40
50
48
92
361CSL1632
125°C/40°C
4 LEAD WYE
// EPA Tier 3 Certified
// Engine-Generator Set Tested to ISO 8528-5 for
Transient Response
// UL2200, CSA Listing Offered
// Accepts Rated Load in One Step Per NFPA 110, Level 1
// All engine-generator sets are prototype and factory tested
// MTU Onsite Energy is a single source supplier
ww/w/ .DGlaotbaSahl Peerot4dUuc.ctoSmupport
// 2 Year Standard Warranty
// 4024HF285 Diesel Engine
- 2.4 Liter Displacement
- Electronic Unit Pump Injection
- 4-Cycle
// Complete Range of Accessories
// Permanent Magnet Generator (PMG) - Optional
- Brushless, Rotating Field
- 300% Short Circuit Capability
- 2/3 Pitch Windings
// Digital Control Panel(s)
- UL Recognized, , NFPA 110
- Complete System Metering
- LCD Display
// Cooling System
- Integral Set-Mounted
- Engine Driven Fan
3 / // / 40-JS6DT3
Application data
// Engine
Manufacturer
Model
Type
Arrangement
Displacement: Cu In (lit)
Bore: in (cm)
Stroke: in (cm)
Compression Ratio
Rated RPM
Engine Governor
Max Power: Standby: bhp (kWm)
Regulation
Frequency
Air Cleaner
// Liquid Capacity (Lubrication)
Total Oil System: gal (lit)
Engine Jacket Water Capacity: gal (lit)
System Coolant Capacity: gal (lit)
// Electrical
Electric Volts DC
Cold Cranking Amps Under 0°F (-17.8°C)
// Fuel System
Fuel Supply Connection Size
Fuel Return Connection Size
Maximum Fuel Lift: ft (m)
Recommended Fuel
Total Fuel Flow: gal/hr (lit/hr)
John Deere
4024HF285
4-Cycle
4-Inline
146 (2.4)
3.4 (8.6)
4.1 (10.5)
18.2:1
1,800
JDEC
80 (60)
±.25%
60 Hz
Dry
2.1 (7.9)
0.68 (2.6)
3 (11.4)
12
750
3/8” NPT
3/8” NPT
10 (3)
Diesel #2
21.7 (82)
www.DataSheet4U.com
// Fuel Consumption
At 100% of Power Rating: gal/hr (lit/hr)
At 75% of Power Rating: gal/hr( lit/hr)
At 50% of Power Rating: gal/hr (lit/hr)
3.7 (14)
2.8 (10.6)
1.9 (7.2)
// Cooling - Radiator System
Ambient Capacity of Radiator: °F (°C)
Max. Restriction of Cooling Air, Intake,
and Discharge Side of Rad.: in. H20 (kPa)
Water Pump Capacity: gpm (lit/min)
Heat Rejection to Coolant: BTUM (kW)
Heat Rejection to Air to Air: BTUM (kW)
Heat Radiated to Ambient: BTUM (kW)
122 (50)
0.5 (0.12)
26 (100)
1,560 (27.4)
484 (8.5)
386 (7)
// Air Requirements
Aspirating: *SCFM (m3/min)
Air Flow Required for Rad.
Cooled Unit: *SCFM (m3/min)
Air Flow Required for Heat
Exchanger/Remote Rad. based
on 25°F Rise: *SCFM (m3/min)
* Air density = 0.0739 lbm/ft3 (1.184 kg/m3)
140 (4)
4,511 (128)
871 (25)
// Exhaust System
Gas Temp. (Stack): °F (°C)
Gas Volume at Stack
Temp: CFM (m3/min)
Maximum Allowable
Back Pressure: in. H20 (kPa)
Minimum Allowable
Back Pressure: in. H20 (kPa)
1,029 (554)
385 (10.9)
30 (7.5)
16 (4)